How to check the Power World Alternator working condition ?


How to check the Power World Alternator working condition ?

1. Too low voltage of the genset under a load
A. Check if the rotary speed of the genset is normal.
B. Check if the UFRO set of AVR is correct.
C. As per the test of excitation separation, check AVR.
D. Damage of rotary diode.
 
2.Too low voltage at free running of the genset
A. Check if the rotary speed of the genset is too low.
B. Check if l -- 2 connection of AVR or outside connected manual micro adjustment is perfect.
 
3.Too High of Output Voltage 
A. Check if the rotary speed of the genset is too high.
B. Check if the load of the genset is of capacitive load (leading power factor). 
 
4. Unstable Output of Voltage of the Genset
A. Check if the rotary speed is stable.
B. Check if the setup of stability is correct. 
 
5. During running of the genset, no voltage outputs 
A. Check the connection ofK1 -- K2 from AVR is correct and reliable.
B. Check the rotary speed of the diesel genset.
C. Check the residual magnetism voltage, charge magnetism if necessary.
D. As per the test of excitation separation, check alternator and AVR.

Hot words: check  Power  World  Alternator  working  

UP: Why choosing Power World diesel generator?
Down:   Power World Fenghuang climbing spirit:Where there is life, there is struggle



Product Advantage
From industrial use and household genset to mobile and Tenancy use genset,power world supply various golden quality genset to meet all kinds of industrial requirements
  • To learn more
  • POWER WORLD | Diesel Generator | Generator Set | Established 1998 www.Dieselgeneratorcn.com © 2015 All Rights Reserved