Why diesel generator consumption of fuel excels the normal level?


Why diesel generator consumption of fuel excels the normal level?
Causes:
A. Block of the air filter, or wrong type.
B. Block of the oil injector, or wrong type.
C. Too low temperature of engine.
D. Improper gap of the air door.
E. Faults or improper setup Of the pressure adjustor.
F. Improper timing of oil supply.
G. Improper adjustment of the oil control rod.
H. Thin air owing to too high ambient temp. or altitude.
I. Overload of engine.
J. Fuel leakages inside or outside.
K. Friction Of ventilation of the fuel box.
L. Friction of the exhaust pipe.
M. Faults on the cold start system.
N. Friction of air door.
O. Low compressive pressure.

Diesel generator consumption of fuel excels the normal level,Remedies:
A. Find out causes/ replace if necessary.
B. Check/adjust or replace the injector.
C. Shown on "temp.of coolant below normal temp".
D. Adjust/check gap of the air door.
E. Repair/readjust.
F. Check the data of the injector and adjust.
G. Check full stroke of throttle.
H. Modify as the sales manual of engine.
I. Check max. load, decrease if necessary.
J. Removal of leakages.
K. Clean /add vent pipe.
L. Inspect friction of the exhaust pipe and proper size.
M. Install the cold start set, check, repair, and replace if necessary.
N. Clean/replace or regrind air door.
O. Shown on "Low compressive pressure".

Hot words: DieselGenerator  generator  

UP: Diesel Generator Emergency Preparedness Month
Down:   Diesel generator electrical control



Product Advantage
From industrial use and household genset to mobile and Tenancy use genset,power world supply various golden quality genset to meet all kinds of industrial requirements
  • To learn more
  • POWER WORLD | Diesel Generator | Generator Set | Established 1998 www.Dieselgeneratorcn.com © 2015 All Rights Reserved